CONDENSATE LOAD, Pounds/Hour
Insulated Steam Main lb/hr of condensate per 100 linear feet at 70oF (at 0oF, multiply by 1.5) |
||||||
Steam Pressure |
Size of Main (inches) |
|||||
(psig) |
2" |
4" |
6" |
8" |
10" |
12" |
| 10 | 6 |
12 |
16 |
20 |
24 |
30 |
| 30 | 10 |
18 |
25 |
32 |
40 |
46 |
| 60 | 13 |
22 |
32 |
41 |
51 |
58 |
| 125 | 17 |
30 |
44 |
55 |
68 |
80 |
| 300 | 25 |
46 |
64 |
83 |
103 |
122 |
| 600 | 37 |
68 |
95 |
124 |
154 |
182 |