HIGH TEMPERATURE
WATER SYSTEMS (HTW) OPERATING
TEMPERATURES AND
PRESSURES
Temperatures and pressures used in HTW systems depend upon the nature of the application. The factors determining the flow temperatures are the highest temperature needed in the system for heating or process requirements and the length of the distribution system. If the length of the distribution system exceeds six miles, it is frequently advisable to maintain a flow temperature substantially greater than that needed so that the pipe size may be reduced. Pressures in the system depend upon the temperatures required and at all times are maintained higher than the saturation pressure corresponding to the water temperature.
- a. Supply and Return Temperature. A supply
- temperature limit of 440 degrees F. is generally
- found to be the economic limit for space and process
- heating because of the high pressures (400 psig)
- required. Higher supply temperatures require rapidly
- increasing pressures throughout the system,
- and while high pressures result in higher heat carrying
- capacities in smaller pipe sizes, the saving in
- pipe size is partially or fully offset by the expense
- of generators, fittings, pipelines and heat exchangers
- strong enough to withstand higher pressures.
- Return water temperatures should be between 250
- degrees F. to 275 degrees F. minimum. Primary
- fuels or alternate fuels with high sulfur content
- can cause generator tubes to corrode. The selection
- of temperatures in the hot water generator during
- all operating conditions should be given special
- considerations with high sulfur content fuels.
- When flue gas is cooled below the dew point, the
- gas side of boiler tubes is subjected to corrosion.
- Corrosion is caused by moisture in the flue gas
- and acids which result from the combination of
- condensed moisture and sulfur compounds in the
- flue gas. The higher the percent by weight of
- sulfur the higher the minimum metal temperature
- must be to prevent this type of corrosion. When it
- is desired to transfer very large heat quantities
- over unusually long distances, an increase in the
- generator pressure to 600 psig corresponding to a
- supply temperature of about 480 degrees F. might
- be justified. For distances up to six miles, the highest
- supply temperature will be selected below 440
- degrees F. The generator supply temperature is
- always maintained somewhat above the temperature
- of the water distributed to the system. In
- steam pressurized systems this is necessary to prevent
- vaporization from taking place if the pumps
- should suddenly be stopped and where the heat
- users are located at elevations higher than the
- generator. The HTW system supply temperature is
- maintained by blending the generator output
- water with the system return water at the pump
- suction header. The HTW generator water is proportioned
- through an automatic mixing valve. Due to heat losses
- from the distribution system piping,
- the supply temperature at the use points will be
- reduced by approximately three to five degrees per
- mile, depending upon the insulation efficiency and
- the amount of water being circulated. The faster
- the water is circulated, the less the temperature
- drops. Process equipment using either direct high
- temperature water or steam produced by converters
- generally requires temperatures at the use
- points ranging from 250 to 400 degrees F. For example,
- some laundry drying equipment requires
- steam pressures of 100 psig which necessitates
- high temperature water of more than 355 degrees
- F. Therefore a heating installation which includes
- such laundry equipment will need a supply temperature
- of at least 375 degrees F. to provide for
- temperature losses and use point requirements
- and a generator pressure of no less than 175 to 200
- psig. It often happens that while temperatures as
- high as these are not needed for space heating,
- they are economical supply temperatures to use
- for lower temperature applications because smaller
- pipe sizes are required. All HTW systems will
- be designed for a minimum of 150 degrees F. differential
- between supply and return water temperatures.
- b. Operating Pressure. This pressure is directly
- related to the operating temperature which is essentially
- equal to saturation temperature in the
- expansion drum in a steam-pressurized system and
- slightly higher in an inert gas-pressurized system.
- Pressure head to overcome frictional and other
- losses must be added to the operating pressure
- when selecting pumps, piping, fittings, and other
- system components. The pumps should never be
- used as part of the pressurization system.