HIGH TEMPERATURE WATER SYSTEMS (HTW) OPERATING
TEMPERATURES AND
PRESSURES

 

Temperatures and pressures used in HTW systems depend upon the nature of the application. The factors determining the flow temperatures are the highest temperature needed in the system for heating or process requirements and the length of the distribution system. If the length of the distribution system exceeds six miles, it is frequently advisable to maintain a flow temperature substantially greater than that needed so that the pipe size may be reduced. Pressures in the system depend upon the temperatures required and at all times are maintained higher than the saturation pressure corresponding to the water temperature.

 

a. Supply and Return Temperature. A supply
temperature limit of 440 degrees F. is generally
found to be the economic limit for space and process
heating because of the high pressures (400 psig)
required. Higher supply temperatures require rapidly
increasing pressures throughout the system,
and while high pressures result in higher heat carrying
capacities in smaller pipe sizes, the saving in
pipe size is partially or fully offset by the expense
of generators, fittings, pipelines and heat exchangers
strong enough to withstand higher pressures.
Return water temperatures should be between 250
degrees F. to 275 degrees F. minimum. Primary
fuels or alternate fuels with high sulfur content
can cause generator tubes to corrode. The selection
of temperatures in the hot water generator during
all operating conditions should be given special
considerations with high sulfur content fuels.
When flue gas is cooled below the dew point, the
gas side of boiler tubes is subjected to corrosion.
Corrosion is caused by moisture in the flue gas
and acids which result from the combination of
condensed moisture and sulfur compounds in the
flue gas. The higher the percent by weight of
sulfur the higher the minimum metal temperature
must be to prevent this type of corrosion. When it
is desired to transfer very large heat quantities
over unusually long distances, an increase in the
generator pressure to 600 psig corresponding to a
supply temperature of about 480 degrees F. might
be justified. For distances up to six miles, the highest
supply temperature will be selected below 440
degrees F. The generator supply temperature is
always maintained somewhat above the temperature
of the water distributed to the system. In
steam pressurized systems this is necessary to prevent
vaporization from taking place if the pumps
should suddenly be stopped and where the heat
users are located at elevations higher than the
generator. The HTW system supply temperature is
maintained by blending the generator output
water with the system return water at the pump
suction header. The HTW generator water is proportioned
through an automatic mixing valve. Due to heat losses
from the distribution system piping,
the supply temperature at the use points will be
reduced by approximately three to five degrees per
mile, depending upon the insulation efficiency and
the amount of water being circulated. The faster
the water is circulated, the less the temperature
drops. Process equipment using either direct high
temperature water or steam produced by converters
generally requires temperatures at the use
points ranging from 250 to 400 degrees F. For example,
some laundry drying equipment requires
steam pressures of 100 psig which necessitates
high temperature water of more than 355 degrees
F. Therefore a heating installation which includes
such laundry equipment will need a supply temperature
of at least 375 degrees F. to provide for
temperature losses and use point requirements
and a generator pressure of no less than 175 to 200
psig. It often happens that while temperatures as
high as these are not needed for space heating,
they are economical supply temperatures to use
for lower temperature applications because smaller
pipe sizes are required. All HTW systems will
be designed for a minimum of 150 degrees F. differential
between supply and return water temperatures.
 
b. Operating Pressure. This pressure is directly
related to the operating temperature which is essentially
equal to saturation temperature in the
expansion drum in a steam-pressurized system and
slightly higher in an inert gas-pressurized system.
Pressure head to overcome frictional and other
losses must be added to the operating pressure
when selecting pumps, piping, fittings, and other
system components. The pumps should never be
used as part of the pressurization system.
Source: U.S. Army, Corps of Army Engineers

 

Return to Technical Reports